Key Takeaway: Selecting the right electronics cooling fan requires more than matching size and published CFM. The following seven inputs will provide a practical starting point: mechanical fit, voltage, airflow, environment, monitoring, speed control and commercial needs. Selecting a fan on paper should then be followed by system-level validation.
Over the years, I have seen many approaches to fan selection. When an engineer contacts me about a cooling application, I start with seven key inputs:
- Available fan dimensions and inlet clearance
- Nominal input voltage and operating range
- Estimated airflow (CFM), if available
- Operating environment (temperature, ingress protection, shock and vibration)
- Required output signals (tachometer and other functions)
- Speed-control requirements (PWM and operating characteristics)
- Commercial requirements (schedule, estimated annual usage and cost target)
Additional questions often come up as the design progresses, but these seven inputs provide a practical starting point.
1. Physical Size and Inlet Clearance
Available space is often one of the first constraints an engineer can define. For example, a 1RU chassis commonly uses 40 mm fans, while a 2RU chassis may accommodate 80 mm fans, depending on the design. Fan depth also matters. In general, a larger fan or a deeper fan of similar design can deliver more airflow or pressure capability, but actual performance depends on the fan design and the system resistance.
Clearance around the fan inlet is just as important as its outer dimensions. In a pull configuration, PCBs and other internal components can restrict air entering the fan. In a push configuration, external obstacles or chassis features can have the same effect. As an initial design guideline, leave generous unobstructed inlet clearance of approximately 1.5 times the fan depth when space allows. Because there is no universal clearance rule that fits every fan and inlet geometry, always validate the final layout through testing.

Dual-rotor fans are also worth considering in compact, high-density systems. Compared with similar single-rotor models, they can provide substantially greater pressure capability and maintain airflow against higher system impedance. Note, they are typically deeper and may consume more power and generate more noise. Some dual-rotor designs provide a degree of fault tolerance, but they should not be assumed to deliver full redundancy, and therefore, confirm failure-mode performance against the system cooling requirement.
2. Nominal Input Voltage and Operating Range
Input voltage is usually straightforward to define. Small fans are available at 5 VDC; 12 VDC is common in IT equipment; 24 VDC is common in industrial applications; and 12 VDC and 48 VDC are both used in telecom and data center equipment. These are general observations, not fixed rules. Although many fans offer a standard ±10% input range, still check the rated and allowable operating voltage range in the specific fan datasheet.
Battery-powered systems may experience a wider supply-voltage range than systems with regulated power rails. Confirm the voltage at the fan under normal operation, startup and transient conditions. If a preferred fan does not meet the requirement, ask whether a different model or a qualified design modification is available.
3. Airflow / CFM Estimate
I have published a separate article in the Resources section of gagner-toomey.com, How to Determine the Right CFM for Electronics Cooling Fans. It explains how engineers can estimate airflow requirements and why the initial fan choice often changes after system-level testing. That article is a useful starting point if you have not yet defined your airflow target.
4. Operating Environment
It is usually easy to describe where a system will operate, but translating that environment into fan requirements takes more work. Temperature, moisture, dust, shock and vibration can all affect fan selection. Delta Electronics offers products designed for different markets and operating environments, including IT/data center, industrial and automotive applications.
Temperature limits are usually set early in the product specification. High temperatures can affect bearing life and electronic components, so it is critical to match the fans’ operating temperature range with your application. Manufacturers can consider (1) selecting a fan with an operating range that accommodates your application or (2) modifying an existing fan by replacing electronic components, bearing systems or lubricants with ones that will withstand elevated operating temperatures. I have also found it helpful when customers define the temperature profile of the application. There is a significant difference between a fan that must operate at 80 °C continuously vs. operating at 80 °C for a maximum of an hour.
Low temperature operation is also an important consideration, since it can affect startup and operation. Do not assume a universal cold-start threshold: verify both operating and startup temperature ratings for the selected model, and share with manufacturer if they do not match.
Ingress protection is important in dusty or wet environments. The two digits in an IP rating describe protection against solid objects and water, respectively. Delta offers selected environmentally protected models with ratings such as those shown below. The rating must be verified for the exact model and installation; a general-purpose fan without a stated IP rating should not be treated as ingress-protected.
| Fan Type | IP Rating | Protection |
|---|---|---|
| Standard general-purpose fans | Not specified | No certified ingress protection established |
| Environmentally protected | IP54 | Dust-protected; resistant to splashing water |
| Environmentally protected | IP55 | Dust-protected; resistant to water jets |
| Environmentally protected | IP56 | Dust-protected; resistant to powerful water jets |
| Environmentally protected | IP67 | Dust-tight; protected against temporary immersion |
| Environmentally protected | IP68 | Dust-tight; protected against immersion under specified conditions |
Shock and vibration requirements are common in vehicles and industrial equipment. These applications may require specialized fan designs or qualification testing. Define the applicable shock and vibration profile early, since the required performance varies widely by application.
5. Output Functionality
The most common output signal I am asked about is the tachometer (tach) output. It allows the system to monitor fan speed and detect abnormal operation, including some fault conditions. A tach signal does not itself control speed; the system uses the signal for monitoring or closed-loop control. The example below illustrates a Delta frequency-generator waveform (i.e., tach output). Check the specific datasheet for pulse count, electrical interface and locked-rotor behavior.

6. Speed Control (PWM and Operating Characteristics)
Engineers can control fan speed in several ways. Reducing the supply voltage may work for certain fans, but it can limit the usable speed range and affect startup. Switching the fan power externally with PWM is another option, although compatibility, noise and reliability depend on the fan design and control method. For fans designed for it, a dedicated PWM control input is often the preferred approach because it provides a defined speed-control interface while the fan receives its rated supply voltage. Minimum speed, startup duty cycle, acoustic behavior and response to a disconnected control lead are model-specific. Although the PWM table (speed vs duty-cycle) typically found in a manufacturer’s PWM spec only defines a few data points, the speed profile is generally linear. The Delta specification below is one example; not a universal PWM standard:

Key points from this example Delta PWM specification:
- Control signal: high level 3 VDC minimum; low level 0.4 VDC maximum; signal range −0.8 to 15 VDC
- Duty cycle = t ÷ T × 100%
- Accepts a control frequency of 30 Hz to 300 kHz; 25 kHz is the preferred operating point
- At 100% duty cycle, the rotor spins at maximum speed
- With the control signal lead disconnected, the fan spins at maximum speed
- At 25 kHz and 30% duty cycle, the fan starts from a dead stop
| Duty cycle (%) | Speed (RPM, ref.) | Current (A, typ.) |
|---|---|---|
| 100 | 5,500 | 4.00 |
| 20 | 1,600 | 0.25 |
| 0 | 1,550 | 0.25 |
7. Commercial Requirements
The more I understand a customer’s production schedule, required delivery dates, estimated annual usage (EAU) and cost targets, the better I can recommend a fan that fits both the design and the program. Early communication also helps us identify lead-time constraints, evaluate alternatives and plan around critical milestones.
These seven inputs give us a solid basis for selecting and evaluating a cooling fan. If you are working through a new design, Gagner-Toomey Associates can help review your requirements and identify suitable options.
Need Help Selecting the Right Cooling Fan?
At Gagner-Toomey Associates, we work with design engineers throughout Northern California and Nevada to help identify Delta Electronics cooling solutions that meet their airflow, static pressure, acoustic and system requirements. Whether you are evaluating fans for a new design or addressing cooling challenges in an existing system, we can help review your requirements and identify suitable options.